This system monitors critical facilities sensors and specialty gas usage on RUMS2.
  • Sensor Status      
  • View all the Graphs      
  • Sensor Configuration & Documentation
  • Return to the NanoLab home page
  • RUMS2 is on-line . Last sampling: 5/16/2012 12:59:06 PM
    Sensor NameDescriptionLow AlarmHigh AlarmCurrent ValueUnitsStatus
    EF_12Lab exhaust alarm (zero indicates no alarm, i.e. exhaust is on). -0.50.50on/off
    EF_34Silane exhaust alarm (zero indicates no alarm, i.e. exhaust is on). -0.50.50on/off
    Low_Level_Gas_WarnLow level gas warning from any zone (zero indicates no warning-level alarms). -0.50.50on/off
    AWN_Chemical_Low_AlarmCheck NaOH and H2SO4 levels on alarm (zero indicates no alarm). -0.50.50on/off
    AWN_General_AlarmState of the Acid Waste Neutralizer general alarm (zero indicates no alarm). -0.50.50on/off
    AWN_Surge_Tank_LevelAcid Waste Neutralizer surge tank level, stage 0. 150450229.47gal
    Compressed_Air_Dew_PointPressure dew point measured at the compressed air source. -112-40-75.38F
    Compressed_Air_General_AlarmGenaral alarm state of the dryer controller (zero indicates no alarm). -0.50.50on/off
    Compressed_Air_N2_BackupState of the CDA N2 backup valve (zero indicates no alarm, i.e. N2 backup is not in use). -0.50.50on/off
    Compressed_Air_PressureThe pressure of the compressed air on the compressor side of the check valve. 90130110.41psi
    DI_General_AlarmState of the DI general alarm (zero indicates no alarm). -0.50.50on/off
    DI_Makeup_FlowRate of flow from the RO system to the DI system. -1251.21gpm
    DI_ResistivityThe final resisitivity of the DI source. 16.518.517.79MOhm-cm
    DI_Tank_LevelDeionized Water tanks level (sum of both tanks). 150023501834.01gal
    PCW_FlowProcess Cooling Water supply flow rate. 35400337.77gpm
    PCW_General_AlarmState of the Process Cooling Water general alarm (zero indicates no alarm). -0.50.50on/off
    PCW_ICW_CrossoverState of the FCV (0 indicates PCW recirc, not crossed over) -0.50.50on/off
    PCW_PressureProcess Cooling Water supply pressure. 5011084.05psi
    PCW_ResistivityResistivity of the PCW loop. 170300244.13kOhm-cm
    PCW_TemperatureProcess Cooling Water supply Temperature. 557062.61F
    Process_VacuumProcess vacuum pressure. 243226.34inHg
    Argon_PressurePre-process argon pressure in 395; pressures less than 40 psi indicate lag bottle is sourcing. 306542.29psi
    N2_Flow_RateFlow rate of N2 at shipping and receiving. 50027001960.89slpm
    N2_Oxygen_ConcentrationOxygen concentration of the process nitrogen. -250.59ppm
    N2_PressureN2 pressure at shipping and receiving. 7510088.57psi
    O2_Flow_rateO2 flow rate at shipping and receiving. -5352.57slpm
    O2_PressureO2 pressure at shipping and receiving. 224533.71psi
    Gas_Cabinet_Alarm_L3State of gas cabinets in the L3 gas vault (zero indicates no alarm). -0.50.50on/off
    Gas_Cabinet_Alarm_L5State of gas cabinets in the L5 gas vault (zero indicates no alarm). -0.50.50.01on/off
    GCAWS_AC_Secondary_H2OWater detection switch in the GCAWS AC trays. -0.50.50on/off
    Lab_3_Relative_HumidityRelative humidity in 384. 207264.28percent
    Lab_3_TemperatureTemperature in 384. 607565.36F
    Lab_5_Relative_HumidityRelative humidity in 584. 207260.29percent
    Lab_5_TemperatureTemperature in 584. 557565.18F
    NH3_599_Weight_lbsWeight of NH3 Cylinder in Rm 599 12518067.65 
    PCW_Pressure_L55th Floor Lab PCW Pressure 408058.9psi
    TestRUMS test channel (for internal use only). -0.50.52.58test